Legionella Tap Temperature Testing Checklist
by Hmp Facilities, from the Community
This weekly checklist guides facilities teams through tap temperature testing to reduce Legionella risk. Log hot and cold sentinel outlet temperatures, confirm hot water cylinder is at least 60 C and return at least 50 C, and verify outlets reach greater than 50 C (hot) within 1 minute and less than 20 C (cold) within 2 minutes. Use results to demonstrate compliance and trigger corrective actions.
With SafetyCulture you can
With SafetyCulture you can
About author
This community page makes available free workplace checklists and templates created by other users within the SafetyCulture community. SafetyCulture has re-published this content and where possible, has credited the original author. SafetyCulture has not verified the accuracy, reliability or suitability of any community content. You agree that your use of any of this content is in accordance with SafetyCulture’s Terms and Conditions.