Underground 12 Week Tank Level Detector Test
by Nyamjav Terbish, from the Community
This Safe Work Instruction outlines the step by step procedure to perform planned online functionality testing of VeriGAP ultrasonic tank level detectors used in underground pump stations. It includes pre start preparations and isolation, required PPE and tools, critical risk controls, and communication steps. Technicians conduct a visual inspection, remove sensor components, perform a dip test to verify relay response, optionally test relay contacts with an ohmmeter, and clean the sensor if needed. The dip test is repeated to confirm results. All findings are logged, the area is cleaned, equipment is returned, and supervisors are notified when detectors are back in operation. Any defects or repairs are documented for follow up.
With SafetyCulture you can
With SafetyCulture you can
About author
This community page makes available free workplace checklists and templates created by other users within the SafetyCulture community. SafetyCulture has re-published this content and where possible, has credited the original author. SafetyCulture has not verified the accuracy, reliability or suitability of any community content. You agree that your use of any of this content is in accordance with SafetyCulture’s Terms and Conditions .