This cast resin transformer maintenance checklist helps technicians document key asset details and complete essential inspections for safe, reliable operation. Record transformer designation, manufacturer, serial number, date of manufacture, voltage, rating, and vector group. Verify operation of interlocks; inspect and secure the outer housing; confirm proper earthing; clear vents; and check the condition and torque of HV and LV terminations and cables. Assess windings, resin, core, internal earthing, and tap connections, and remove dust and debris. Review protection settings including current alarm and trip, and test temperature alarm and trip. Conclude by confirming all tools and equipment are removed from the work area.
With SafetyCulture you can
With SafetyCulture you can
About author
This community page makes available free workplace checklists and templates created by other users within the SafetyCulture community. SafetyCulture has re-published this content and where possible, has credited the original author. SafetyCulture has not verified the accuracy, reliability or suitability of any community content. You agree that your use of any of this content is in accordance with SafetyCulture’s Terms and Conditions.